Annual 250,000-tonne Lysine Project – High-Voltage Soft Starter

Project Characteristics

Specialised Load: Steam turbine generator. Process involves utilising the turbine to drive the generator to 95% of rated speed, followed by flywheel start-up via the soft starter to achieve full rated speed. Upon reaching rated speed, the soft starter disengages from the main circuit, enabling the generator to reverse power and synchronise with the grid.

On-site Load Conditions

10kV 12,000kW steam turbine generator set × 1;